PROCESS CONNECTION INSTALLATION
The standard process connection for the AST46DS is ½” NPT male. Use the
7/8” hex above the thread of the process connection to install into the process.
Do not use the body / housing for installation.
ELECTRICAL INSTALLATION
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or the area
is known to be non-hazardous. This equipment must be powered by a Non-
hazardous live source in accordance with CAN/CSA-C22.2 No. 61010-1-04 eg.
limited energy source, or a Class 2 Source.
Please review the following wiring instructions. For U.S. installations, product
case ground screw on the interior or exterior of the housing must be bonded to
ground according to Article 501 & 505 of the NEC.
Recommended Wire Gauge: 18-22 AWG
Remove rear cover by hand to access terminal blocks.•
Run wire through either conduit connection and feed toward the terminal blocks. •
Conduit should be installed over wire / cable per electrical code requirements.
Use a Philips Head screw driver to loosen terminal screws.•
Connect wires to the proper terminal according to chart and tighten screw.•
Ensure either the internal or exterier case ground screw is • bonded to ground
according to Article 501 & 505 of the NEC.
Install conduit plug if one side of electrical connection is unused.•
Close Cover.•
WIRING INFORMATION
Output Type Pin 1 Pin 2 Pin 3
Electrical Power
Requirement
1-5V +V -V Signal Output 8-28VDC
4-20mA +Signal - Signal Not Connected 8-28VDC
PIN 1
PIN 2
PIN 1
PIN 2
PIN 3
7/8’ Hex
1/2’ NPT Male
FIELD SERVICE
TheAST46DShasnoeldserviceableparts.Fortechnicalissuesorquestions,
please contact the factory: [email protected]

1/2” NPTF1/2” NPTF
6.535
4.134
1.556
3.543
4.173
1.575
case ground screw
TERMINAL BLOCK OUTLINE